Leviton OSC20-M0W Installation Instructions

• To be installed and/or used in accordance with appropriate electrical codes and regulations.

• If you are unsure about any part of these instructions, consult a qualified electrician.

• Sensors must be mounted on a vibration free surface.

• All sensors must be mounted at least 6 feet away from air vents.

• Do not mount sensors closer than 10 feet from each other.

• Do not touch the surface of the lens. Clean outer surface with a damp cloth only.

Tools needed to install your Sensor:

Slotted/Phillips Screwdriver

Electrical Tape

Parts Included List:

Threaded Rod (1) and Hex Nut (1)

#8-32 x 1/2" Screw (2)

Half Mask (1)

#8-32 x 1-1/2" Screw (2)

360° Perforated Mask (1)

#8-32 Washer and Nut (2)

Plastic Washer (1)

DESCRIPTION

The Occupancy Sensor is a low-voltage infrared and ultrasonic sensor that works with

the OSP xx Series and CN100 power pack to automatically control lighting. The sensor

turns the lights on and keeps them on whenever occupancy is detected and will turn

them off after the 'delayed-off time' has expired.

The sensor continually analyzes and adjusts to changing conditions. The sensor uses

the latest microprocessor-based technology which permits it to continually adjust and

optimize its performance.

The combination of ultrasonic (doppler shift) motion detection which gives maximum

sensitivity and infrared motion detection which gives higher false triggering immunity

yields a sensor with excellent performance.

INSTALLING YOUR OCCUPANCY SENSOR

NOTE: Use check boxes

when Steps are completed.

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER

at circuit breaker or fuse and test that power is off before wiring!

Preparing and connecting wires:

(if necessary)

Strip Gage (measure

bare wire here)

Typical Installations:

Listed are 3 typical installation options (A, B, and C). Choose one that best suits

your needs. Other methods of installation may be possible but they have not been

described here.

A. Drop Ceiling Installation (Mounting Option A):

NOTE: Use the threaded rod included.

1. Select location for mounting of sensor and proper masking for your application

(refer to Mounting Location Diagram).

2. Use the supplied threaded rod or other methods to make a hole (1/2" to 1") in the

ceiling tile just large enough to pass the body of the threaded rod through.

3. Insert the sensor wires through the flared end of the threaded rod. Position the

threaded rod to the base of the sensor.

4. Insert the flared end of the threaded rod into the opening in the bottom of the

sensor and twist to lock into place.

Multi-Technology Ceiling Mounted Occupancy Sensor

Cat. No. OSCØ5-M, OSC1Ø-M, OSC2Ø-M

To be used with 24VDC OSP xx Series and CN100 Power Pack Class II Low-Voltage Wiring

INSTALLATION INSTRUCTIONS

Catalog No.

Description

1-Way Multi-Technology

2-Way Multi-Technology

2-Way Multi-Technology

Step 3 cont'd

5. Push the wires into the hole in the ceiling tile and insert the threaded rod until the

sensor is flush with the tile.

6. Insert wires through the hole in the included washer, then place the included

washer over the rod and screw on the included hex nut.

7. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per

WIRING DIAGRAM as follows: Twist strands of each lead tightly and, with circuit

conductors, push firmly into appropriate wire connector. Screw connectors on

clockwise making sure that no bare conductor shows below the wire connectors.

Secure each connector with electrical tape.

8. Rotate the sensor to the desired orientation. Note that the sensor base and back

cover are keyed. To lock the device in place, ensure that the arrows are not aligned.

9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS

Mounting Option Diagram A

Occupancy Sensor Mounted to Drop Ceiling Using Threaded Rod

Low-Voltage Wires

Drop Ceiling

1" thick maximum

Threaded Rod

NOTE: Wires routed through

the Threaded Rod

B. Wallboard or Drop Ceiling Installation (Mounting Option B):

NOTE: You may use the mounting screws, nuts and washers included, or screws in

combination with commercially available wall anchors.

1. Select location for mounting of sensor and proper masking for your application

(refer to Mounting Location Diagram).

2. Make a hole in the ceiling tile or wallboard large enough to pass the wire

connections and wire nuts through (approximately 1" diameter).

3. Remove the back cover of the sensor. Hold the back cover and body of the sensor

and rotate until the two arrows line up and pull apart.

4. Install back cover of the ceiling sensor to the wallboard or drop ceiling using the

included screws, nuts and washers, or screws in combination with commercially

available wall anchors.

5. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per

WIRING DIAGRAM as follows: Twist strands of each lead tightly and, with circuit

conductors, push firmly into appropriate wire connector. Screw connectors on

clockwise making sure that no bare conductor shows below the wire connectors.

Secure each connector with electrical tape.

6. Push wire connections through the center hole of the back cover and into the ceiling.

7. Secure the sensor body to the back cover by aligning the arrows. Lock it by

turning the sensor such that the arrows do not line up.

8. Rotate the sensor to the desired orientation.

9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS COMPLETE.

Mounting Option Diagram B

Occupancy Sensor Mounted to Wallboard

or Drop Ceiling Using Screws

Low-Voltage Wires

Low Voltage Wires

Nut (2 places)

Washer (2 places)

Back Cover

Wallboard Ceiling

Mounting Screws

Keylock Arrow

Sensor Base

Sensor Front Cover

CATALOG ITEMS

Consumption

Mounting Location

Mount in corner/

over doorway

Mount in center

1000 sq. ft.

of room/area

Mount in center

2000 sq. ft.

of room/area

Step 3 cont'd

C. Junction Box or Surface Mount Raceway Installation (refer to

Mounting Diagrams):

NOTE: Listed below are suggested JUNCTION BOX installation applications which

require mounting to conduit in one of the following three ways:

Occupancy Sensor Mounted to Octagon

Box Installed Flush to Wallboard Ceiling

Octagon Box

4" x 1 1/2" deep

#8-32 Screws

Wallboard or

Drop Ceiling

TABLE 2: WIRE DESIGNATIONS

Temp/Voltage

200° C/ 600V

200° C/ 600V

200° C/ 600V

Occupancy/Photocell

200° C/ 600V

Back Cover open center to

route Low-Voltage Wires

120/277/347VAC

Mounting Screw

Back Cover internal

surface shown

Back Cover shown mounted

Neutral (White)

on ceiling with screws

FCC COMPLIANCE STATEMENT:

his device complies with part 15 and part 18 of the FCC rules. Operation is subject to the following two

conditions: (1) This device must not cause harmful interference, and (2) This device must accept any

interference received, including interference that may cause undesired operation.

Step 3 cont'd

Occupancy Sensor Mounted to Round Fixture

with Raceway for Wallboard Installation

Wire Mold Round Fixture